SLIDE 1 / (HOOK / COVER) ⚡ NEC Quick Hit: Continuity of Power & Locked-Rotor Sizing (Part 3) ⚡
Why must fire pump overcurrent protective devices be sized to carry locked-rotor current indefinitely? Section 695.5 has strict rules to keep power flowing during a fire. Let's break it down! 👇
Minimizing Inadvertent Disconnection:
Direct Connection Preferred: The best way to maintain power continuity is connecting the source directly to the listed fire pump controller without intermediate disconnects.
Single Disconnect Allowance: If a disconnect and OCPD are installed between the source and controller, they must be limited to a single disconnecting means (except for campus feeders or standby generators).
Carrying the Load Indefinitely:
Sizing for LRC: OCPDs for individual sources must be rated to carry indefinitely the sum of the locked-rotor current (LRC) of the largest fire pump motor plus full-load currents of other pumps and accessories.
Mandatory Supervision: Disconnecting means must be marked "Fire Pump Disconnecting Means" in 1-inch red letters and supervised in the closed position via central station signal, local alarm, lock, or seal.
💡 Apprentice Pro-Tip: Standard motor OCPDs are designed to thermal-trip during an overload, but a fire pump breaker must never thermal-trip on locked-rotor current. It must hold indefinitely so the pump can fight the fire until destruction!