"How many degrees can you bend EMT before you're breaking code?"
Min size: metric designator 16 (trade size 1/2") — exception: 3/8" for motor lead enclosures [358.20(A)]
Max size: metric designator 155 (trade size 6") [358.20(B)]
Conductor fill follows Chapter 9, Table 1 [358.22]
Bends: max 360° total between pull points [358.24(B)]
Reaming required on all cut ends — EMT cannot be threaded (unless factory-threaded) [358.28]
Securing: fastened within 3 ft of every box and every 10 ft along the run [358.30(A)]
Quick Quiz: 1️⃣ What's the max total bend degrees allowed between pull points? 2️⃣ Can you thread EMT in the field?
💬 Test yourself — answer in the comments! 🔔 Follow @JoshTheSparky for more NEC breakdowns 📌 Save & share with your crew