2026 NEC ARTICLE 265
We've covered:
⚡ 265.1 — Scope
⚡ 265.4 — Specific-purpose circuits
⚡ 265.5 — Conductor identification
⚡ 265.6 — Voltage limitations
⚡ 265.9 — Autotransformers
⚡ 265.10 — Tapped conductors
⚡ 265.11 — Branch circuits required
⚡ 265.18 — Circuit rating
⚡ 265.19 — Conductor ampacity
⚡ 265.20 — OCP
⚡ 265.22/.23 — Permissible loads
⚡ 265.63 — Servicing equipment
Don't memorize Article 265 as a giant list of numbers.
Understand the flow:
WHAT CIRCUIT?
⬇️
DOES 265 APPLY?
⬇️
WHAT EQUIPMENT?
⬇️
HOW ARE CONDUCTORS IDENTIFIED?
⬇️
HOW IS THE CIRCUIT RATED?
⬇️
WHAT AMPACITY IS REQUIRED?
⬇️
WHAT OCP IS REQUIRED?
⬇️
WHAT OTHER ARTICLES APPLY?
That's NEC navigation.
A 1200V ac branch circuit has a designed simultaneous load of 80A.
Under the general requirements we've studied, which pairing is correct?
A.
Conductor ampacity: 80A
OCPD: 125A
B.
Conductor ampacity: 100A
OCPD: 80A minimum
C.
Conductor ampacity: 80A
OCPD: 80A minimum
D.
Conductor ampacity: 125A
OCPD: 60A
Conductor ampacity:
80A × 125% = 100A
OCPD:
100% of the simultaneous load
= 80A minimum
The important lesson isn't just the math.
It's knowing which requirement you're applying to which part of the circuit.
⚡ ARTICLE 265 COMPLETE
📚 NEXT UP: ARTICLE 266
FOLLOW FOR MORE DAILY QUICK HIT STUDY NOTES
JoshTheSparky.com
This gives you 18 short-form episodes with a logical progression from scope → conductor identification → voltage limitations → transformers → circuit ratings → ampacity → OCP → loads → servicing → final review.
And the series naturally sets us up for the next article: 2026 NEC Article 266 — Feeders Over 1000 Volts ac, 1500 Volts dc, Nominal.