Slide 1 — Hook "This is the biggest single section in the whole article. We're splitting it into two episodes — starting with GROUNDED separately derived systems."
Slide 2 — The big picture
A separately derived system = a system with no direct electrical connection to another supply (like the secondary of a transformer, or a generator not solidly tied to utility power).
Key rule: on the load side of the system bonding jumper, the grounded conductor can NEVER be reconnected to ground, to equipment grounding conductors, or to non-current-carrying metal parts — that would create a dangerous parallel path.
Slide 3 — System bonding jumper & grounding electrode
The system bonding jumper connects at ONE point — either at the source, or at the first disconnect/OCPD — and stays inside that originating enclosure.
It connects the grounded conductor to the supply-side bonding jumper and either the metal enclosure (if at the source) or the disconnect enclosure + EGCs (if at the first disconnect).
The grounding electrode used is the building/structure's grounding electrode system (or, if the source is outdoors, an electrode at that outdoor location).
Multiple separately derived systems can share ONE common grounding electrode conductor, with individual tap conductors run to each system.
Slide 4 — Quiz + CTA Q: "On the load side of a separately derived system's bonding jumper, can the grounded conductor be reconnected to ground?" A) Yes, anywhere convenient B) No — that would create a dangerous parallel path C) Only if a licensed engineer approves it D) Only for systems under 5000V
✅ Answer: B — 270.30(A) prohibits this reconnection on the load side.
CTA: Follow for more daily quick-hit study notes 📚⚡