UNGROUNDED CONDUCTORS TAPPED FROM GROUNDED SYSTEMS
265.10 permits certain:
🔹 Two-wire DC circuits
and
🔹 AC circuits with two or more ungrounded conductors
to be tapped from ungrounded conductors of a circuit having a grounded neutral conductor.
Here's the part to watch:
Each ungrounded conductor of the tapped circuit must have a pole in the switching device.
And when a multipole switching device serves as the disconnecting means:
all poles must manually switch together.
265.10 references requirements involving:
🔹 Lampholders
🔹 Electric-discharge lighting equipment
🔹 Appliances
🔹 Electric space heating
🔹 Deicing/snow melting
🔹 Motor controllers
🔹 Motors
Again...
FOLLOW THE CROSS-REFERENCES.
A tapped AC branch circuit has multiple ungrounded conductors.
What does 265.10 require regarding switching?
A. Only the grounded conductor must be switched
B. Each ungrounded conductor must have a pole in the switching device
C. No switching is permitted
D. Only one ungrounded conductor can be switched
ANSWER: B