2026 NEC Reference: 230.4(A)–(E)
The one-service rule has several important exceptions.
Additional services are allowed for certain special conditions, including:
Fire pumps
Emergency systems
Legally required standby systems
Optional standby systems
Interconnected power production sources
Certain multiple-source reliability arrangements
Special permission from the AHJ can also allow additional services in certain situations.
Additional service arrangements can also apply when:
The calculated load exceeds 2000 amperes at 1000V or less
A single-phase load exceeds what the utility normally supplies on one service
Different voltages are required
Different frequencies are required
Different phases are required
Different rate schedules justify separate service
Name one special-condition load that can justify an additional service.
Answer:
Fire pumps, emergency systems, legally required standby systems, optional standby systems, or interconnected power production sources.
The rule is one service, but Article 230 gives you specific paths to additional services.
Know the exceptions.
➡️ Next Quick Hit: Service conductors, buildings, and what counts as "outside."