Slide 1 — Hook "New Part! Today: what actually counts as a grounding electrode, and the rule that ties them all together."
Slide 2 — 270.50 The system concept
Every qualifying grounding electrode present at a building/structure has to be bonded together to form ONE grounding electrode system.
If none of the "naturally occurring" electrode types exist, you have to install one of the other permitted types.
Slide 3 — 270.52 The electrode types (permitted)
Metal underground water pipe (10+ ft in earth contact, electrically continuous)
Metal in-ground support structures (10+ ft vertical earth contact — pilings, casings, etc.)
Concrete-encased electrode ("Ufer ground") — 20+ ft of rebar (½"+ diameter) or bare 4 AWG+ copper, encased in 2"+ of concrete
Ground ring — 20+ ft of bare 2 AWG+ copper encircling the building
Rod/pipe electrodes — 8+ ft long, specific material/diameter rules
Other listed electrodes
Plate electrodes — 2+ sq ft of soil exposure, specific thickness rules
Other local metal underground systems (piping, tanks, well casings not bonded to a water pipe)
NOT permitted: metal gas piping, aluminum, or certain pool-related structural rebar.
Slide 4 — Quiz + CTA Q: "A concrete-encased electrode ('Ufer ground') using rebar must be at least how long?" A) 10 ft B) 20 ft C) 30 ft D) 6 ft
✅ Answer: B — 270.52(A)(3): at least 20 ft (6.0 m).
CTA: Follow for more daily quick-hit study notes 📚⚡