2026 NEC References: 230.5, 230.6, 230.7, 230.8, 230.9, 230.10
Service conductors have specific rules when they travel between buildings and when they're considered outside a building.
Service conductors supplying one building cannot pass through the interior of another building.
They can run along the exterior of one building to supply another, but the building being supplied needs its own disconnect.
Examples include conductors:
Under at least 2 inches of concrete
Encased in at least 2 inches of concrete or brick
In a qualifying vault
Under at least 18 inches of earth
Through an eave using RMC or IMC under the applicable conditions
Service conductors generally can't share a raceway, cable, or handhole with other non-service circuit conductors.
There are specific exceptions, including grounding electrode conductors and certain load-management control conductors.
Service raceways entering a building must be sealed.
Open service conductors and jacketless cable also have clearance requirements from operable windows, doors, and similar openings.
And remember:
Trees aren't service-conductor support structures.
How much earth cover makes buried service conductors count as "outside the building" when installed in conduit beneath the building?
Answer: 18 inches (450 mm) or more.
Know the difference between inside, outside, and entering the building.
➡️ Next Quick Hit: Overhead service conductors.