Slide 1 — Hook "New Part! Construction Specifications — starting with the two Type MV temperature classes, and insulation thickness for nonshielded conductors."
Slide 2 — 315.10(A) The two Type MV classes
MV-90: 90°C max operating temperature, dry or wet locations, thermoplastic or thermosetting insulation, with a jacket/sheath/armor outer covering.
MV-105: 105°C max — used specifically where design conditions require conductor temperatures above 90°C.
Same basic concept as Article 310's insulation type table, just condensed to two entries since medium-voltage cable construction is more standardized than the huge low-voltage type list.
Slide 3 — 315.10(B) Nonshielded insulation/jacket thickness (2001V-5000V)
Table 315.10(B) scales insulation and jacket thickness by conductor size — generally getting THICKER as the conductor gets larger, split into dry-location (with/without jacket) and wet-or-dry-location (single conductor vs. multiconductor) columns.
Pattern to know: at the smallest sizes (8 AWG-2/0), dry-location insulation-without-jacket sits at 110 mils; it climbs to 140 mils by the 1001-2000 kcmil range. Wet-location single-conductor insulation runs even thicker — starting at 125 mils and climbing similarly.
Slide 4 — Quiz + CTA Q: "What's the maximum operating temperature for Type MV-105 cable?" A) 90°C B) 105°C C) 125°C D) 150°C
✅ Answer: B — 315.10(A): MV-105 is rated for 105°C.
CTA: Follow for more daily quick-hit study notes 📚⚡