Slide 1 — Hook "Closing out Part VI — disconnecting the grounded conductor, how disconnects get operated, their rating, and what's allowed ahead of the service disconnect."
Slide 2 — 268.75, 268.76, 268.77, 268.79, 268.81
268.75: if the disconnect doesn't disconnect the grounded conductor itself, another means (like a pressure-connector terminal/bus) has to be provided for that purpose in the service equipment.
268.76: the disconnect must be either manually operable (switch/fused cutout/breaker with a handle) or power-operated — AS LONG AS power-operated types can still be opened by hand if power fails.
268.77: must plainly show open (off) vs. closed (on).
268.79: continuous current rating ≥ the minimum required ampacity of the service-entrance conductors (per 268.42).
268.81: service-entrance conductors connect to the disconnect via pressure connectors, clamps, or other approved means — never solder-dependent connections.
Slide 3 — 268.82 What CAN sit on the supply side of the disconnect Only a specific list: cable limiters; instrument transformers/impedance shunts/load management devices/surge arresters; conductors for energy management systems, standby power, fire pump equipment, and fire/sprinkler alarms (if built into service equipment); solar/fuel cell/wind/energy storage/interconnected power sources (with their own compliant disconnect + OCP); control circuits for power-operable disconnects; ground-fault protection systems; and protective relay control power circuits — each of the last three needing their own suitable OCP and disconnecting means.
Slide 4 — Quiz + CTA Q: "Can a power-operated service disconnect be opened by hand if there's a power supply failure?" A) No, power-operated disconnects can never be manually opened B) Yes — this capability is required C) Only with a special tool no one has access to D) Only in emergency systems
✅ Answer: B — 268.76(2): power-operated disconnects must be openable by hand in a power failure.