Welcome back to Article 215 — Feeders!
How do you identify feeder conductors when a building has multiple voltage systems? Can multiple feeders share a common neutral?
In this episode, we'll cover conductor identification, feeder diagrams, and common neutral conductors.
Feeder conductors must be identified in accordance with the applicable NEC requirements.
Grounded conductors are identified in accordance with 200.7.
Equipment grounding conductors are identified in accordance with 250.119.
Where a building has a single voltage system, the standard conductor identification provisions described in 310.6(A)(3) apply.
Where multiple voltage systems are present, each ungrounded feeder conductor must be identified by phase or line and system voltage at each termination point.
Identification may use methods such as:
Color coding
Tape
Tags
The identification scheme must be documented or posted at the originating panelboard, as described in the source material.
The source material describes polarity identification requirements for DC systems over 60 volts:
Conductors 6 AWG and smaller: red for positive and black for negative, or approved lettering.
Conductors 4 AWG and larger: polarity identification must be documented at terminations.
When required by the authority having jurisdiction (AHJ), a feeder diagram must be provided before installation.
The diagram includes information such as:
The square footage served.
Total calculated load before and after demand factors.
The demand factors used.
Conductor size and type.
A feeder diagram helps document the design and load calculations for the feeder installation.
Article 215 permits certain feeder sets to share a common neutral conductor.
The limits described in this episode are:
Feeder configuration
Maximum sets sharing one common neutral
3-wire feeders
3 sets
4-wire or 5-wire feeders
2 sets
When feeders sharing a common neutral are installed in a metal raceway or enclosure, all feeder conductors sharing that neutral must be grouped together in the same raceway or enclosure.
This helps prevent induction heating concerns.
Question: How many sets of 4-wire feeders can share a single common neutral conductor?
A) One
B) Two
C) Three
D) Unlimited
Under the limits described in 215.14(A), up to two sets of 4-wire or 5-wire feeders may share a common neutral conductor.
For comparison, the source material describes a limit of three sets for 3-wire feeders.
Proper feeder identification is especially important in buildings with multiple voltage systems. Article 215 also addresses feeder diagrams and limits how many feeder sets can share a common neutral.
Follow for more daily quick-hit study notes!
📚 Next: Episode 5 — Barriers & Surge Protection, the Article 215 Finale.