Slide 1 — Hook "New Part! Installation — starting with WHO is allowed to install medium-voltage cable, and where Type MV cable itself is permitted to go."
Slide 2 — 315.30 Installation by qualified persons
Type MV cable installation AND testing must be done by qualified persons with documented training/experience.
Cable JOINTS specifically need qualified persons trained/experienced in JOINT installation.
Cable TERMINATIONS specifically need qualified persons trained/experienced in TERMINATION installation.
Worth flagging: for DC medium-voltage circuits, low-frequency polarization can create hazardous residual voltages on the cable — solidly grounding the cable before contacting/cutting/disconnecting it is the standard way to discharge that risk.
Slide 3 — 315.32(A) Where Type MV cable is permitted (up to 35,000V) Wet or dry locations; in raceways; in cable trays (if identified for the use, per several cable tray citations — cable marked "MV or MC" gets extra flexibility here); in messenger-supported wiring; as exposed runs per 305.12 (same "MV or MC" flexibility applies); in corrosive conditions if suitable for that exposure; in parallel per 310.10(G); exposed to direct sunlight if identified for that use; and direct buried per 315.36.
Slide 4 — Quiz + CTA Q: "Before contacting, cutting, or disconnecting DC medium-voltage cable, what precaution helps discharge hazardous residual voltage?" A) Wearing insulated gloves only B) Solidly grounding the cable first C) Waiting 24 hours D) No special precaution is needed for DC cable
✅ Answer: B — the informational note to 315.30 recommends solidly grounding the cable to discharge low-frequency-polarization voltages.
CTA: Follow for more daily quick-hit study notes 📚⚡