SLIDE 1 (HOOK / COVER)
⚡ NEC Quick Hit: Snap Switches & Electronic Controls (Part 4) ⚡
3-way/4-way wiring, neutral wire requirements at switch boxes, height limits, and switch load ratings—let's finish Article 406! 👇
SLIDE 2 (SWITCH CONNECTIONS & NEUTRALS)
Smart Switches and Switch Loops:
Ungrounded Conductors: Three-way and four-way switches must switch only ungrounded circuit conductors.
Neutral Conductor at Switches: A grounded circuit conductor (neutral) must be installed at lighting switch locations serving bathrooms, hallways, stairways, and habitable rooms to support electronic control switches.
Height & Grouping: Switches must be readily accessible with operating handles not more than 2.0 m (6 ft 7 in.) high. When ganged in boxes, voltages exceeding 300V between adjacent devices require identified barriers.
SLIDE 3 (RATING AND USE OF SWITCHES)
Controlling Specific Loads:
Motor Loads: AC general-use snap switches can control motor loads up to 80 percent of their ampere rating.
LED & Electronic Ballasts: Permitted for electronic ballasts, LED drivers, and compact fluorescents up to 20 amperes (not exceeding the switch rating).
Dimmer Restrictions: Dimmers are restricted to controlling permanently connected loads unless specifically listed for other equipment.
SLIDE 4 (WRAP-UP) 💡 Apprentice Pro-Tip:
Always pull a neutral wire into your switch boxes on new installations—modern smart switches, timers, and occupancy sensors require that neutral standby power to function properly!
💬 Save this post for your final code review on Wiring Devices!
🔗 More code breakdowns and study tools at www.JoshTheSparky.com