PART 6 OF 30 — NEC 120.7(C)(1) | PCS MONITORING ONLY CONTROLLED LOADS
NEC 120.7(C)(1) EXPLAINED ⚡
WHEN A PCS CONTROLS ONLY ITS LOADS
joshthesparky4 · Josh The Sparky
⚡ OPENING HOOK
When a PCS only monitors what it controls...
The calculation changes. ⚠️
🧠 CORE IDEA
⚡ NEC 120.7(C)(1) allows a different load calculation method when a Power Control System (PCS) monitors ONLY the controlled loads within its system.
Instead of adding all connected loads together...
⚡ The PCS control setting is used.
This reflects how the system will actually operate in real time.
⚡ CODE CONNECTION
When conditions are met:
✅ The PCS monitors only controlled loads
✅ No uncontrolled loads are included in that system
Then:
⚡ The PCS control setting replaces total connected load in calculations
Because the system will automatically limit demand before overload occurs.
📌 REAL-WORLD EXAMPLE
🔌 EV Charger #1 = 40A
🔌 EV Charger #2 = 40A
🔌 EV Charger #3 = 40A
⚡ Total connected load = 120A
But the PCS limits operation to:
⚡ 80A maximum control setting
📌 For calculations:
➡️ Use 80A
❌ Not 120A
Because the PCS will never allow the system to exceed that value.
📌 CORE TAKEAWAY
⚡ PCS-controlled systems can replace connected load with control settings.
⚡ This only applies when ALL monitored loads are controlled.
⚡ The system’s actual limit becomes the design value.
⚡ FINAL LINE
You don’t calculate what’s connected...
You calculate what’s allowed to run. ⚡