Episode 9.5
We already met office receptacle loads back in 120.14(J).
Now we're looking at the feeder/service-level version — and there's an extra step involved.
At the feeder/service level, office receptacle loads are calculated using the larger of:
1️⃣ The 120.14(I) calculated load
But there's an important detail:
Table 120.47 demand factors are applied first.
OR
2️⃣ 1 VA per square foot
11 VA/m²
The branch-circuit-level calculation and the feeder/service-level calculation aren't identical.
At this level, the 120.14(I) calculated load can have the applicable Table 120.47 demand factors applied before the comparison is made.
Here's the good news:
Certain loads in hotel and motel guest rooms and suites are already included in the Table 120.42(A) unit load.
That means they don't require a separate calculation.
✅ General-use receptacle outlets rated 20 amperes or less
✅ Receptacle outlets covered by 210.52(E)(3)
✅ Lighting outlets covered by 210.70
For these specified hotel and motel guest-room loads, the Table 120.42(A) unit load already accounts for them.
One number covers it all.
A) Motor outlets over 1/8 hp
B) General-use 20-ampere-or-less receptacle outlets
C) Sign and outline lighting
D) Show-window loads
👇 What's your answer?
B) General-use 20-ampere-or-less receptacle outlets
These specified receptacle outlets are already included in the Table 120.42(A) unit load, so a separate load calculation isn't required for them under 120.44.
← Back to Article 120 Quick Hits
→ Office Receptacle Loads
→ Table 120.47 Demand Factors
→ Hotel & Motel Guest Room Loads
🧠 Brain Busters — Test your knowledge
❓ Question of the Week — Take the weekly NEC challenge
📖 Tutorials — Go deeper
This Quick Hit is an educational explanation based on the author's understanding of the NEC. It is not a substitute for the official NEC, applicable local amendments, manufacturer instructions, or the determination of the Authority Having Jurisdiction (AHJ).
Always verify the requirements applicable to your specific installation.