Episode 9
We already looked at office receptacle loads at the branch-circuit level in 120.14(J).
Now we're moving up to the feeder/service level — and there's an extra step.
We'll also look at how certain receptacle and lighting outlets in hotel and motel guest rooms are handled within the unit load.
At the feeder/service level, the receptacle load for office buildings is the larger of:
But there's an important step:
Apply the applicable Table 120.47 demand factors first.
OR
1 VA/ft²
or approximately
11 VA/m²
Whichever calculated value is larger is used.
This is where the feeder/service calculation differs from the branch-circuit calculation.
120.14(J)
120.43
At the feeder/service level, the Table 120.47 demand factors are applied to the 120.14(I) calculated load before making the comparison with the 1 VA/ft² value.
Calculate → Apply demand factor → Compare
Hotel and motel guest rooms and suites have another special provision.
Certain outlets are already included in the Table 120.42(A) unit load.
That means they don't require a separate load calculation under this provision.
General-use receptacle outlets rated 20 amperes or less
210.52(E)(3) receptacle outlets
210.70 lighting outlets
For these specified guest-room loads:
They're already baked into the Table 120.42(A) unit load.
No separate calculation is needed for those outlets under 120.44.
A) Motor outlets over 1/8 hp
B) General-use 20-ampere-or-less receptacle outlets
C) Sign and outline lighting
D) Show-window loads
👇 What's your answer?
B) General-use 20-ampere-or-less receptacle outlets
These specified general-use receptacles are already included in the Table 120.42(A) unit load.
Hotel/Motel Guest Room
➡️ Table 120.42(A) unit load
➡️ Certain receptacle and lighting outlets are already included
➡️ No separate calculation for those specified outlets under 120.44
Continue exploring the JoshTheSparky Quick Hits library.
Test what you know with the JoshTheSparky Brain Busters.
Take the latest JoshTheSparky Question of the Week.
Go deeper into electrical thoughts, lessons, discoveries, and experiences in Sparky's Journal.
Follow the latest progress, discoveries, projects, and industry updates in Sparky Weekly.
Review the references and resources used throughout JoshTheSparky.com in the JoshTheSparky Sources library.
← Back to Article 120 Quick Hits
This Quick Hit is an educational explanation based on the author's understanding of the NEC. It is not a substitute for the official NEC, applicable local amendments, manufacturer instructions, or the determination of the Authority Having Jurisdiction (AHJ).
Always verify the requirements applicable to your specific installation.