Episode 37 — 120.88 Optional Method for New Restaurants
We've covered optional calculation methods for:
🏠 Single dwelling units
🏚️ Existing dwelling units
🏢 Multifamily buildings
🏘️ Two-unit buildings
🏫 Schools
📊 Existing installations using recorded demand
Now Article 120's Part IV optional methods reach their final stop:
And this one has an interesting split.
Section 120.88 provides an optional method for a new restaurant where the feeder serves the entire restaurant load.
Instead of using the standard Part III calculation method, the applicable Table 120.88 method can be used.
But, as always with an optional method:
Don't automatically apply the table to every restaurant installation.
Using the optional restaurant method doesn't eliminate the other applicable NEC requirements.
Service-conductor overload protection remains subject to the applicable requirements, including 230.90 and 240.4.
The feeder conductors don't have to be larger than the service conductors under the applicable rule.
The neutral calculation can still be determined under:
So the optional restaurant method changes the applicable load calculation method — it doesn't erase the rest of the electrical requirements.
This is the big feature of Table 120.88.
The table separates restaurants into two categories:
The restaurant's applicable equipment is electrically supplied.
The restaurant has applicable loads that aren't entirely electric.
And the two categories don't receive the same demand factors.
The table recognizes differences in how the restaurant's connected load is expected to operate.
That's why you can't simply memorize:
“Restaurants get X%.”
Instead, you first need to determine:
Then:
Then:
For a total connected load of:
80%
100%
That's a major difference.
At this first tier, an all-electric restaurant receives a demand factor while the not-all-electric restaurant is calculated at the full 100%.
The next tier changes from a simple percentage into a formula.
10% of the amount over 200 kVA
+ 160.0 kVA
50% of the amount over 200 kVA
+ 200.0 kVA
So once the connected load passes 200 kVA, you aren't simply multiplying the entire load by one percentage.
The calculation uses the amount above the threshold plus the applicable base value.
This is another example of an NEC calculation that uses tiers.
Think:
⬇️
Different factor depending on restaurant type
⬇️
⬇️
Percentage applied to the amount over 200 kVA
⬇️
Additional Table 120.88 formulas apply.
The source material available for this Quick Hit has a portion of Table 120.88's closing note cut off.
The text ends with an instruction to:
multiply the total connected load by [missing multiplier]
Because that multiplier isn't available in the source material, it should NOT be guessed.
That's exactly the kind of detail that can turn an otherwise useful code-study resource into bad information.
Use the verified portions only.
A not-all-electric restaurant has a total connected load of:
That's within the:
0–200 kVA
range.
For a not-all-electric restaurant, the applicable demand percentage is:
Therefore:
150 kVA × 100% = 150 kVA
Per Table 120.88, a not-all-electric restaurant has a total connected load of 150 kVA.
What demand percentage applies?
A) 80%
B) 100%
C) 50%
D) 10%
👇 Comment your answer!
A not-all-electric restaurant with a total connected load in the 0–200 kVA range uses the 100% demand factor from the applicable portion of Table 120.88.
🍔 NEW RESTAURANT
⬇️
🏗️ Feeder serves the whole load
⬇️
📊 Optional Table 120.88
⬇️
All-electric or not-all-electric?
⬇️
Determine the applicable connected-load tier.
⬇️
0–200 kVA
🔥 All-electric → 80%
🍽️ Not-all-electric → 100%
With 120.88, we've reached the end of the optional calculation methods covered in Part IV of this series.
120.80 — Optional calculation methods introduced
120.82 — Single dwelling units
120.83 — Existing dwelling units
120.84 — Multifamily dwelling units
120.85 — Two dwelling units
120.86 — Schools
120.87 — Existing installations using recorded demand
120.88 — New restaurants
Article 120 doesn't stop here.
We're now moving into:
The next section takes us into agricultural installations and introduces another set of specialized load-calculation rules.
Continue the Article 120 series at JoshTheSparky Quick Hits.
Test yourself with JoshTheSparky Brain Busters.
Try the latest JoshTheSparky Question of the Week.
Explore Sparky's Journal.
Catch the latest Sparky Weekly.
Review the references behind the site's educational content in JoshTheSparky Sources.
← Episode 36 — Using REAL Data Instead of Math
→ Episode 38 — Part V: Farm Load Calculations
← Back to Article 120 Quick Hits
Episode 25: Welcome to Part IV — Optional Calculations
Episode 26: Who Even Gets to Use This Shortcut?
Episode 27: Bucket #1 — General Loads
Episode 28: Bucket #2 — Heating & AC (Part 1)
Episode 29: Bucket #2 — Heating & AC (Part 2)
Episode 30: Bucket #3 — EVSE + Putting It All Together
Episode 31: Existing Dwelling Units
Episode 32: Multifamily Buildings
Episode 33: Multifamily Demand Factor Table
Episode 34: Two-Unit Buildings
Episode 35: Schools
Episode 36: Existing Installations Using Recorded Demand
Episode 37: New Restaurants ← PART IV FINALE
Episode 38: Farm Load Calculations — Coming Next