Episode 21 — 120.55 Electric Cooking Appliances
We've made it through the big cooking-appliance rules.
But what happens when you're dealing with just one appliance?
Or maybe you've got a cooktop and multiple wall ovens sharing one branch circuit?
The notes to 120.55 cover these situations — and each one has a different approach.
What if you're calculating the branch-circuit load for a single range?
There's a specific cross-reference:
⚠️ Notice the distinction:
This isn't telling you to use Table 120.55 for the single-range branch-circuit calculation.
It's pointing you to Table 220.55.
One range
↓
Table 220.55 permitted
Now take a single:
Wall-mounted oven, or
Counter-mounted cooking unit
when it's being considered by itself.
The branch-circuit load is simply:
No demand-factor table is needed for this particular calculation.
One wall oven → Nameplate
One counter-mounted cooking unit → Nameplate
Now things get interesting.
Suppose you have:
PLUS
And they're:
On the same branch circuit
In the same room
What do you do?
Then treat the combined rating:
Counter-mounted cooking unit:
6 kW
Wall oven #1:
4 kW
Wall oven #2:
5 kW
Combined nameplate rating:
6 + 4 + 5 = 15 kW
That combined 15 kW is treated as one range for purposes of the applicable calculation.
Don't treat the three appliances as three completely independent loads for this particular provision.
The rule specifically allows the combination to be treated as:
after adding their nameplate ratings.
A counter-mounted cooking unit and two wall-mounted ovens are all:
In the same room
On the same branch circuit
Per Note 6, how should their combined load be treated?
A) As 3 separate appliances, each calculated individually
B) As one range, using the sum of their nameplate ratings
C) Using Table 220.55 only
D) At 1¾ kW flat, regardless of nameplate rating
👇 What's your answer?
Suppose the appliances are rated:
Cooktop: 6 kW
Wall oven #1: 4 kW
Wall oven #2: 5 kW
Add the nameplates:
6 + 4 + 5 = 15 kW
Under Note 6, the combined rating is treated as:
The counter-mounted cooking unit and up to two wall-mounted ovens can be combined when they're on the same branch circuit and in the same room.
Their nameplate ratings are added together and the combined load is treated as one single range.
You've now seen several different methods within the same section:
Use the applicable Table 120.55 methodology and its notes.
The alternative method can use Column A or Column B under the applicable conditions.
Table 220.55 is permitted for the branch-circuit calculation.
Nameplate rating.
Add the nameplates and treat the combination as one range when the specified conditions are met.
Continue exploring the JoshTheSparky Quick Hits library.
Test what you know with the JoshTheSparky Brain Busters.
Take the latest JoshTheSparky Question of the Week.
Go deeper into electrical thoughts, lessons, discoveries, and experiences in Sparky's Journal.
Follow the latest progress, discoveries, projects, and industry updates in Sparky Weekly.
Review the references and resources used throughout JoshTheSparky.com in the JoshTheSparky Sources library.
← Back to Article 120 Quick Hits
← Episode 20 — The 1¾–8¾ kW Shortcut
→ Episode 22 — Instantaneous Water Heaters
This Quick Hit is an educational explanation based on the author's understanding of the NEC. It is not a substitute for the official NEC, applicable local amendments, manufacturer instructions, or the determination of the Authority Having Jurisdiction (AHJ).
Always verify the requirements applicable to your specific installation.