Article: 120 — Load Calculations
Part: Part IX — Mobile and Manufactured Homes
Section: 120.141
Format: Quick Hit
We calculated the load for one mobile home in the last few episodes.
Now we're looking at the load calculation for an entire mobile home park.
Section 120.141 provides demand factors that account for diversity between multiple mobile homes connected to the same park wiring system.
⚠️ Source Verification Note: The final row of Table 120.141 — "61 and over" — is missing its demand-factor percentage in the source material used for this Quick Hit.
Rather than guessing the missing NEC value, it is intentionally left unidentified.
Park wiring is calculated at 120/240 volts using the larger of these two values:
Start with:
➡️ 16,000 VA per mobile home lot
OR:
Use the actual calculated load from 120.140 for the largest typical mobile home that each lot is intended to accommodate.
The calculation uses whichever is larger:
16,000 VA per lot
OR
Actual 120.140 load
The idea is to make sure the park wiring is sized for the greater of the standard baseline or the actual expected mobile-home load.
Once the baseline load has been established, Table 120.141 applies demand factors based on the number of mobile homes.
➡️ 100%
No diversity discount.
➡️ 55%
A major drop occurs once multiple homes are included.
➡️ 33%
The demand factor continues dropping as the number of homes increases.
➡️ 27%
➡️ 24%
➡️ 23%
➡️ Demand factor not available in the source material
⚠️ The supplied source text does not include the percentage for the "61 and over" row.
No percentage has been guessed or substituted.
This is the same basic diversity concept we've seen throughout Article 120.
A park with one mobile home has to account for essentially the entire calculated load.
But as the number of homes increases, it becomes less likely that every home will simultaneously demand its maximum calculated load.
So the demand factor decreases as the number of homes increases.
Think:
More homes
⬇️
More diversity
⬇️
Lower percentage of the calculated total
There's an important restriction attached to this table:
No demand factor is permitted for any other load in the park beyond what is specifically provided for by the Code.
In other words:
🚐 Mobile-home loads → Table 120.141
Other park loads → Don't automatically apply this demand factor
You can't simply take every load connected to the park and start applying the mobile-home demand factor to it.
When you see 120.141, remember:
🏘️ Mobile home park
⚡ 120/240V
🔢 Larger of 16,000 VA per lot OR actual 120.140 load
📊 Table 120.141
📉 More homes = lower demand factor
⚠️ No demand factor for other park loads unless specifically permitted
And remember:
1 home → 100%
2 homes → 55%
5 homes → 33%
10–12 → 27%
22–40 → 24%
41–60 → 23%
61+ → source value unavailable
Per Table 120.141, what demand factor applies to a mobile home park with exactly 3 mobile homes?
A) 55%
B) 44%
C) 39%
D) 33%
B) 44%
A park with 3 mobile homes falls into the applicable 3–4 mobile homes range of Table 120.141, which uses a 44% demand factor.
That's it.
49 Episodes. 9 Parts. One Article.
We've gone from the opening rules of Article 120 all the way through the final mobile-home-park demand factor.
✅ Part I — General rules
Voltages, rounding, floor area, noncoincident loads, PCS
✅ Part II — Branch-circuit loads
Dwellings and outlet-specific calculations
✅ Part III — Feeder & service loads
Lighting, receptacles, dryers, ranges, EVSE, neutral calculations
✅ Part IV — Optional methods
Existing dwellings, multifamily buildings, schools, restaurants
✅ Part V — Farm loads
✅ Part VI — Health care facilities
✅ Part VII — Marinas, boatyards, floating buildings & docking facilities
✅ Part VIII — RV parks
✅ Part IX — Mobile & manufactured homes
From 120.1 all the way to 120.141.
That's a LOT of load calculations.
And hopefully by now...
Load calcs don't kill you. 🔌⚡
Continue the Article 120 Quick Hits:
🌐 www.JoshTheSparky.com/quick-hits
Test yourself with Brain Busters:
🧠 www.JoshTheSparky.com/brain-busters
Answer the Question of the Week:
❓ www.JoshTheSparky.com/question-of-the-week
Read Sparky's Journal:
📓 www.JoshTheSparky.com/sparkys-journal
Catch the latest Sparky Weekly:
📰 www.JoshTheSparky.com/sparky-weekly
View Sources & References:
📚 www.JoshTheSparky.com/Sources
Primary: Article 120, 120.141
Related: 120.140 — Mobile and Manufactured Homes Load Calculation
Related: Table 120.141 — Allowable Demand Factors
The supplied source material does not include the demand-factor percentage for the "61 and over" row of Table 120.141.
No percentage has been guessed or substituted.
Once the complete table is available, the missing value can be added.
Article 120 — Load Calcs Won't Kill You
Episode 49: Allowable Demand Factors
THE END. 🏆🔌⚡